IRANTECH 300-CT

IRANTECH 300-CT

Smart 3-Phase Secondary Connection- IRANTECH 300-CT

IRANTECH 300-CT is a 3-phase indirect meter designed to measure active/reactive energy, maximum demand and real-time parameters and etc.
Some of the key capabilities of the IRANTECH 300-CT meter include:

  • Monthly/daily billing
  • Multi-tariffs
  • load profile
  • Detecting and recording events
  • Neutral measurement (optional)
  • Supply control
  • Ability to add different modules such as GPRS, PLC, and RF modules which supports plug and play without power off the meter.

 

 Technical Specifications


Description

Value
Insulation strength
AC voltage test
Insulation strength4kV at 50Hz 1 min
Impulse voltage strength
Impulse voltage 1.2/SOμs mains connections8kV
Protection class II
Display
Display typeLCD (liquid crystal display)
Number of digits value fieldUp to 8
Digit size4.48?8.4
Inputs and Outputs
Optical test outputs active energy & reactive energy
TypeRed LED(SMD)
Pulse width30ms
Active energy constant10000 imp/kWh
Reactive energy constant10000 imp/kvarh
Communication Interface
Optical interface
Communication standardsIEC62056á21 E mode - HDLC
Boud rate for IEC62056-21 E mode


boud rate for HDLC
300~115200 bps(configurable)
9600bps(default)

9600bps
IHD interface
Communication standardsDLMS HDLC
Baud rate4800-9600-19200 bps(configurable)
9600(default)
MBUS interface
Communication standardsEN 13757-2
Baud rate2400 bps
Plug.in interface
For different communication medium
Include GPRS/PLC/RF/ZigBee
RS-485 interface
Communication standardsDLMS HDLC
Baud rate4800-9600-19200 bps(configurable)

Description

Value
Voltage
Nominal voltage Un3x230/400V
Extended operating voltage range0.7Un~1.2Un
Start operating voltage145
Limiting voltage520
Frequency
Nominal frequency fn50Hz
Tolerance45Hz to 55Hz
Current
Basic current (Ib)1A
Maximum current (Imax)10A
Starting current (Ist)5mA
Measurement Accuracy
Active energyClass 0.5
Reactive energyClass 2
Power Consumption
Power consumption in Voltage circuit
Active power without module<2W
Apparent power without module<10VA
Power consumption in current circuit
Apparent power without module<0.5VA
Environmental Influences
Temperature range
Operation meter-40'C to +80'C
Storage-40'C to +85'C
Electromagnetic Compatibility
Electrostatic discharges
Contact discharge8kV
Electromagnetic RF fields
27 MHz to 500 MHzTypical 10V/m
100 kHz to 1 GHzTypical 30V/m
Fast transient burst testNormally 4kV
PDF Catalogue
Online Catalogue