IRANTECH 300-DC/ Smart 3-Phase Direct Meter
The IRANTECH 300-DC is a 3-phase direct meter designed to measure active energy, reactive energy, maximum demand and real-time parameters.
Some of the key capabilities of the IRANTECH 300-DC meter include:
- Monthly/daily billing
- Multi-tariffs
- load profile
- Detecting and recording events
- Neutral measurement (optional)
- supply control
- Ability to add different modules such as GPRS, PLC, and RF modules which supports plug and play without power off the meter.
Technical Specifications
|
|
---|---|
Insulation strength | |
AC voltage test | |
Insulation strength | 4kV at 50Hz 1 min |
Impulse voltage strength | |
Impulse voltage 1.2/SOμs mains connections | 8kV |
Protection class II | |
Display | |
Display type | LCD (liquid crystal display) |
Number of digits value field | Up to 8 |
Digit size | 4.48x8.4 |
Inputs and Outputs | |
Optical test outputs active energy & reactive energy | |
Type | Red LED(SMD) |
Pulse width | 30ms |
Active energy constant | 1000 imp/kWh |
Reactive energy constant | 1000 imp/kvarh |
Communication Interface | |
Optical interface | |
Communication standards | IEC62056-21 E mode - HDLC |
Boud rate for IEC62056á21 E mode boud rate for HDLC | 300~115200 bps(configurable) 9600bps(default) 9600bps |
IHD interface | |
Communication standards | DLMS HDLC |
Baud rate | 4800-9600-19200 bps(configurable) 9600(default) |
MBUS interface | |
Communication standards | EN 13757-2 |
Baud rate | 2400 bps |
Plug.in interface | |
For different communication medium Include GPRS/PLC/RF/ZigBee | |
RS-485 interface | |
Communication standards | DLMS HDLC |
Baud rate | 4800-9600-19200 bps(configurable) |
|
|
---|---|
Voltage | |
Nominal voltage Un | 3x230/400V |
Extended operating voltage range | 0.7Un~1.2Un |
Start operating voltage | 145 |
Limiting voltage | 520 |
Frequency | |
Nominal frequency fn | 50Hz |
Tolerance | 45Hz to 55Hz |
Current | |
Basic current {lb) | 10A |
Maximum current (lmax) | 100A |
Starting current (1st) | 40mA |
Measurement Accuracy | |
Active energy | class 1 |
Reactive energy | class 2 |
Power Consumption | |
Power consumption in Voltage circuit | |
Active power without module | <2W |
Apparent power without module | <10VA |
Power consumption in current circuit | |
Apparent power without module | <0.5VA |
Environmental Influences | |
Temperature range | |
Operation meter | -40'C to +80'C |
Storage | -40'C to +85'C |
Electromagnetic Compatibility | |
Electrostatic discharges | |
Contact discharge | 8kV |
Electromagnetic RF fields | |
27 MHz to 500 MHz | Typical 10V/m |
100 kHz to 1 GHz | Typical 30V/m |
Fast transient burst test | Normally 4kV |