Irantech12 DL is a single-phase digital meter designed and produced to meet the requirements of TAVANIR 3.1 edition. This meter is equipped with two optical and RS485 communication ports and supports DLMS protocol.
Additionally, Irantech12 DL enables HHU devices to read data through the optical port with IEC62056-21 protocol, Readout mode to provide accurate invoices.
The meter can also read data in the form of AMR by using a GPRS modem.
By using Irantech12 DL meter, electricity distribution companies can access data on voltage, current, energy and power that are stored on FAHAM MDM 24/7.
Technical Specifications
Description
Value
Voltage
Nominal voltage Un
230V
Extended operating voltage range
0.85Un~1.15Un
Start operating voltage
140
Limiting voltage
460
Frequency
Nominal frequency fn
50Hz
Tolerance
45Hz to 55Hz
Current
Basic current (Ib)
5A
Maximum current (Imax)
100A
Starting current (Ist)
<20mA
Measurement Accuracy
Active energy
Class 1
Reactive energy
Class 2
Power Consumption
Power consumption in Voltage circuit
0.3W
Power consumption in current circuit
<0.1VA
Inputs and Outputs
Optical test outputs active energy & reactive energy